Technical Specification
MODEL UPT-IOTRT10000
- VA/Watt – 10KVA/10KW
INPUT PERFORMANCE
- Voltage range (Phase voltage) – 110Vac-276Vac
- Nominal Frequency – 220/230/240VAC
OUTPUT PERFORMANCE
- Rated voltage (Phase voltage) – 220/230/240VAC
- Overload on normal mode – 105%-125% Load, 10 minutes transfer to Bypass;
125%-150% Load, 30 seconds transfer to Bypass;
>150% Load, 0.5 seconds transfer to Bypass - Short-circuit current on normal mode – 113A for 200ms max
Transfer Time Line <-> Battery – 0ms
Transfer Time Inv<-> Bypass- 0ms
Battery Voltage – 240VDC
Battery Number – 20PCS
Other Mode
- CVCF – Yes (derating to 60% load)
HMI
- Display – Dot matrix LCD (optional segment LCD)
COMMUNICATION
- Port – USB, RS232, Dry in/out, RPO, IOT Ethernet port
- Monitor Software – Winpower, Winpower View APP
DIMENSION (W*D*H) mm – 438*540*86.3
ENVIRONMENT
- Ambient Temperature – o⁰C ~ 50⁰C (Derating 50% above 40⁰C)