TRIPP LITE provides UL 60601-1 compliant, medical-grade 700VA/450W power backup, ideal for use in patient-care vicinities. The built-in isolation transformer offers full isolation while maintaining AC surge protection in all modes.
- Supports a half load up to 36 minutes; full load up to 14.5 minutes
- Six IEC320 C13 hospital-grade outlets and IEC320 C14 hospital-grade plug
- Leakage current less than 100 microamps
- Approved for use within the Patient Care Vicinity
- Approved to EN60601-1-2:2015, 4th Edition
- 340 joule surge suppression rating protects connected equipment
- Alarm mute/alarm quiet control is ideal for use around patients
- 2-year warranty
OVERVIEW
| UPC Code |
037332140418 |
| UPS Type |
Line-Interactive |
OUTPUT
| Output Volt Amp Capacity (VA) |
700 |
| Output Watt Capacity (Watts) |
450 |
| Nominal Voltage Details |
230V nominal inverter output voltage |
| Frequency Compatibility |
50 / 60 Hz |
| Frequency Compatibility Details |
Automatic frequency selection |
| Output Voltage Regulation (Line Mode) |
-18%, +8% |
| Output AC Waveform (Battery Mode) |
PWM sine wave |
| Nominal Output Voltage(s) Supported |
220V; 230V; 240V |
| Output Receptacles |
(6) C13 |
| Individually Controllable Load Banks |
No |
INPUT
| Rated input current (Maximum Load) |
3.6A |
| Nominal Input Voltage(s) Supported |
230V AC |
| UPS Input Connection Type |
C14 inlet |
| UPS Input Cord Length (ft.) |
0.50 |
| UPS Input Cord Length (m) |
0.2 |
| Recommended Electrical Service |
10A 230V |
| Voltage Compatibility (VAC) |
230 |
| Input Phase |
Single-Phase |
BATTERY
| Full Load Runtime (min.) |
14.5 min. (450w) |
| Half Load Runtime (min.) |
36 min. (225w) |
| DC System Voltage (VDC) |
36 |
| Battery Recharge Rate (Included Batteries) |
Less than 3.6 hours from 10% to 90% (typical, full load discharge) |
| Internal UPS Replacement Battery Cartridge |
RBC36SLT |
| Battery Access |
The battery access door allows hot swap battery replacement without powering connected equipment off |
| Typical Battery Lifespan |
3-6 years, depending on usage |
| Expandable Runtime |
No |
VOLTAGE REGULATION
| Voltage Regulation Description |
Line interactive UPS offers 2 boost levels of brownout correction and a single level of overvoltage adjustment to maintain usable, computer-grade output without consuming battery power over an input voltage range of 155 to 274V AC |
| Overvoltage Correction |
Input voltages between 206 and 245V AC are reduced by 9% |
| Undervoltage Correction |
Input voltages between 183 and 199 are boosted by 10% |
| Severe Undervoltage Correction |
Input voltages between 155 and 182 are boosted by 21% |
USER INTERFACE, ALERTS & CONTROLS
| Switches |
Yes, includes 2 front panel-mounted push-button switches for system enable, self-test and alarm cancel functions |
| Audible Alarm |
The 3-function audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous short beeps) & low battery (continuous tone). Audible Alarm is factory muted for silent operation; Audible alarm can be restored to indicate power failure, overload conditions, & Low Battery events, using our Free PowerAlert UPS management software. |
| LED Indicators |
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status |
SURGE / NOISE SUPPRESSION
| UPS AC Suppression Joule Rating |
340 |
| EMI / RFI AC Noise Suppression |
Yes |
| AC Suppression Response Time |
Instantaneous |
PHYSICAL
| Cooling Method |
Cooling via rear-exit cooling fan |
| Installation Form Factors Supported with Optional Accessories |
Wallmount (“UPSWM” – tower mounting kit) |
| Primary Form Factor |
Tower |
| Primary UPS Depth (mm) |
229 |
| Primary UPS Height (mm) |
325 |
| Primary UPS Width (mm) |
191 |
| Shipping Dimensions (hwd / cm) |
46.99 x 30.99 x 33.99 |
| Shipping Weight (kg) |
20.59 |
| UPS Housing Material |
PVC |
| UPS Power Module Dimensions (hwd, cm) |
32.51 x 19.05 x 22.86 |
| UPS Power Module Weight (kg) |
19.10 |
ENVIRONMENTAL
| Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
| Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
| Relative Humidity |
0 to 95%, non-condensing |
| AC Mode BTU / Hr. (Full Load) |
208.6 |
| Battery Mode BTU / Hr. (Full Load) |
189.1 |
COMMUNICATIONS
| Communications Interface |
USB; DB9 Serial |
LINE / BATTERY TRANSFER
| Transfer Time |
5 milliseconds |
| Low Voltage Transfer to Battery Power (Setpoint) |
155 |
| High Voltage Transfer to Battery Power (Setpoint) |
274 |
SPECIAL FEATURES
| Grounding Lug |
Equipotential connection (back panel grounding lug) |
| Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
CERTIFICATIONS
| UPS Certifications |
CE; Tested to UL60601-1 (medical grade) |
WARRANTY
| Product Warranty Period (International) |
2-year warranty |